UPS SINE WAVE (M) – RN Online SERIES – UPS RN2400C
| Product Category | : | UPS SINE WAVE (M) |
| Product Series | : | RN Online SERIES |
| Product Name | : | UPS RN2400C |
| Harga | : | Call Of Price |
ICA UPS RN2400C Capacity 2400VA. Because the UPS is the true on-line system, conditioned power is provided continuously to the attached load. The UPS constantly regulates and filter the AC input voltage and supply a clean and stable AC voltage to the output and charge the batteries. When the AC input voltage low or loss, the UPS protects the load instantaneously and supply a stable AC voltage without any transfer time.
TECHNICAL INFORMATION
| Description | : | UPS RN2400C |
| Capacity | : | 2400 VA / 1200 W |
| AC Voltage | : | 160 – 250 V |
| AC Frequency | : | 50 ± 3 Hz |
| AC Protection | : | 10 A |
| DC Voltage | : | 72 V |
| DC INT Battery | : | 6 x 12 V, 7 Ah |
| DC Protection | : | FUSE |
| CHG Topology | : | SWITCHING REGULATION |
| CHG Floating Voltage | : | 81.6 V |
| INV Waveform | : | SINEWAVE |
| INV Distorsion | : | < 3% THD |
| INV Topology | : | PULSE WIDTH MODULATION (PWM) |
| INV Voltage | : | 220 ± 2% V |
| INV Frequency | : | 50 Hz |
| INV Efficiency | : | > 85% |
| Transfer Time AC Fail | : | 0 ms |
| Transfer Time STS | : | 2 ms INVERTER TO BYPASS |
| : | ZERO CROSSING BYPASS TO INVERTER | |
| Back Up Time | : | 10 min |
| Buzer AC In Abnormal | : | INTERMITTENT SOUND WITH 4 SECONDS INTERVAL |
| Buzer Battery Low | : | INTERMITTENT SOUND WITH 1 SECONDS INTERVAL |
| Opera Temp | : | 0 – 40 °C |
| Dimension (DxWxH) | : | 550 x 435 x 176 mm |
| Weight | : | 35 Kg |